Categories | Motor Protector Relay |
---|---|
Rated control supply voltage | AC380V. AC220V. 50Hz/60Hz |
Contact capacity | Ith:5A;AC-15;Ue/Ie 380V/0.95A 240V/1.5A |
Setting mode | Button setting |
IP Class | IP20 |
Use category | AC-15 |
Starting avoid time | 2s~ 120s adjustable |
Tripping class | 1、2(10A)、 3(10)、 4(20)、5(30) |
Protection | Overload, current unbalance, phase loss, temperature |
Convertion time | 2s~ 900s adjustable |
Current unbalance rate | 20%~ 90% adjustable |
Update Time | September 27,2023 |
Detail Information
Function
Applications
Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection of over-voltage, under voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off power supply to protect the equipment.
Built-in microprocessor,current measurement accuracy ≤2%.Button setting,double LED digital display. With three-phase current inquiry and protectionof overload, phase failure, unbalance and temperature. Support power-offself-staring, two-speed motors, star-delta starter.No-load start,protection of any phase loss or overload.No contact protection.

Wiring Diagram